Analysis of transients in the medium voltage supply circuit of a high-current laboratory

Authors

  • Jolanta Sadura Institute of Theory of Electrical Engineering, Measurement and Information Systems Warsaw University of Technology Pl. Politechniki 1, 00-661 Warsaw, Poland https://orcid.org/0000-0001-9612-550X
  • Jan Sroka Institute of Theory of Electrical Engineering, Measurement and Information Systems Warsaw University of Technology Pl. Politechniki 1, 00-661 Warsaw, Poland https://orcid.org/0000-0003-3210-3904
  • Jacek Starzyński Faculty of Electronic Military University of Technology ul. gen. Sylwestra Kaliskiego 2, 00 – 908 Warsaw 46, Poland https://orcid.org/0000-0002-1093-9500

DOI:

https://doi.org/10.24425/aee.2026.156810

Abstract

Electric and magnetic field measurements performed in the high-current laboratory (HCL) revealed recurring disturbances in the form of damped oscillations. An analysis of the test procedures and a detailed investigation of the system configuration indicated that the likely cause of these disturbances was the asynchronous operation of contacts in a medium-voltage (MV) vacuum circuit breaker. This hypothesis was verified using both field and circuit simulations. The non-uniform test circuit of the HCL was represented as a cascaded equivalent model based on segmentation and distributed electrical parameters. The obtained simulation results confirmed the proposed hypothesis and highlighted the significant impact of the switching process on the generation of electromagnetic disturbances in the MV supply path.

Downloads

Published

2026-02-12

How to Cite

Sadura, Jolanta, et al. “Analysis of Transients in the Medium Voltage Supply Circuit of a High-Current Laboratory”. Archives of Electrical Engineering , vol. 75, no. 1, Feb. 2026, pp. 191-05, doi:10.24425/aee.2026.156810.

Issue

Section

Article

Similar Articles

<< < 7 8 9 10 11 12 13 14 15 16 > >> 

You may also start an advanced similarity search for this article.